Martindale VI13800 Voltage Indicator
Clear voltage indication. No batteries, switches or range settings.
The Martindale VI13800 Voltage Indicator supports proving dead as part of a safe isolation procedure before electrical maintenance or installation work. Powered by the circuit under test, it provides automatic AC/DC voltage detection without batteries to replace or a range selector to set.
Bright LEDs indicate four voltage thresholds: 50, 100, 200 and 400 V. The instrument’s published voltage range is 50–600 V AC/DC, with retractable locking probe shrouds, finger guards and a double-insulated cable designed for practical site use.
Request a Martindale VI13800 quote today. Tell us your required quantity and whether you also need a proving unit.
Martindale VI13800 Voltage Indicator Key Features:
- Self-powered operation: draws power from the circuit under test, with no batteries required
- Stepped LED indication: clear AC/DC voltage and polarity indication
- Automatic detection: no switches or selectable ranges
- Retractable locking probe shrouds: with heavy-duty finger guards
- Visible cable damage indication: a contrasting white inner core helps highlight damage to the double-insulated cable
- Non-fused protection: a resistor in the probe limits current at the point of contact
- CAT IV 600 V rating: with Class II double insulation and IP54 protection
Why choose the Martindale VI13800 Voltage Indicator?
Choose a dedicated voltage indicator that keeps instrument settings simple. The VI13800 combines automatic detection with a clear LED display, helping your team focus on the required checks within its safe isolation procedure.
Its retractable probe shrouds, finger guards and contrasting cable core support a practical design for electrical work. The result is a straightforward instrument to specify for individual electricians or wider maintenance teams.
What Comes with the Martindale VI13800 Voltage Indicator?
- Martindale VI13800 Voltage Indicator, manufacturer part number MARVI13800
- Instruction manual
| Features | |
| Identification and Electrical Performance |
| Model | VI13800 |
| Manufacturer part number | MARVI13800 |
| Voltage range | 50–600 V AC/DC |
| Nominal LED voltage thresholds | 50, 100, 200 and 400 V DC/AC rms |
| Nominal voltage threshold tolerance | Conforms to BS EN 61243-3:2014 |
| AC/DC and range detection | Automatic |
| Polarity indication | ✓ |
| Frequency range | DC, 1 to 400 Hz |
| Response time | <0.1 s |
| Test current | 3.5 mA maximum at 600 V AC/DC |
| Internal impedance at ELV AC | 214 kΩ |
| Duty ratio | 30 s ON (operated) / 240 s OFF (recovery) |
| Power supply | From the circuit under test; no batteries required |
| Construction and Safety |
| Probe shrouds | Retractable and locking |
| Cable | Double insulated, with a contrasting white inner core |
| Overcurrent protection | Non-fused; current-limiting resistor in the probe |
| Overvoltage category | CAT IV 600 V |
| Insulation | Class II, double insulation |
| Safety standards and guidance | BS EN 61243-3; BS EN 61010-1; GS38 |
| Protection rating | IP54 to BS EN 60529 |
| Operating Conditions and Physical Details |
| Operating temperature | -10 to +55 °C |
| Storage temperature | -20 to +70 °C, non-condensing |
| Operating and storage humidity | ≤85% RH |
| Altitude | Up to 2,000 m |
| Pollution degree | 2 |
| Dimensions (L × W × D) | 205 × 67 × 27 mm |
| Weight | 190 g |
| Warranty | 2 years |
❓ Frequently Asked Questions (FAQ)
Q1: Does the Martindale VI13800 need batteries?
A. No. It takes its power from the circuit under test. Voltage and range detection are automatic.
Q2: Does the VI13800 display an exact voltage reading?
A. It uses LEDs to indicate fixed voltage thresholds of 50, 100, 200 and 400 V. It does not provide a numerical meter reading.
Q3: Is a proving unit included?
A. No. This listing includes the VI13800 and its instruction manual. Martindale specifies that a voltage indicator used for proving dead should be checked with a proving device.
Request a Quote for the Martindale VI13800 Voltage Indicator
Equip your team with a dedicated voltage indicator for its safe isolation procedures. Quote MARVI13800 and your required quantity when contacting us.
Enquire today for a Martindale VI13800 quotation.