Megger FRAX200 Sweep Frequency Response Analyser
Detect Transformer Winding and Core Faults with Confidence
The Megger FRAX200 Sweep Frequency Response Analyser is designed to identify mechanical and electrical faults inside power transformers before they become costly failures. Using proven Sweep Frequency Response Analysis (SFRA) technology, the Megger FRAX200 helps maintenance engineers assess transformer condition quickly, accurately and with excellent repeatability.
Whether you‘re commissioning a new transformer, carrying out routine maintenance or investigating a suspected fault, the Megger FRAX200 provides reliable diagnostic data to support informed maintenance decisions.
Contact our team today for pricing, expert advice or a quotation on the Megger FRAX200.

Why Choose the Megger FRAX200?
The Megger FRAX200 measures the frequency response of transformer windings and cores by injecting a swept sine wave and analysing the resulting signal. The measurement creates a reference ‘fingerprint‘ that can be compared with previous results to identify internal mechanical changes over time.
Designed for field and workshop use, the Megger FRAX 200 combines high measurement accuracy with simple operation. Features such as built-in demagnetisation, automatic ground loop checking and Bluetooth connectivity help improve testing efficiency while reducing the risk of inaccurate results.
Megger FRAX200 Key Features:
The Megger FRAX offers a range of features designed to simplify transformer diagnostics, including:
- Sweep Frequency Response Analysis from 0.1 Hz to 30 MHz
- Built-in adaptive demagnetisation for improved low-frequency measurements
- Automatic ground loop verification before every test
- USB-C and Bluetooth Low Energy (BLE) communication
- Battery-powered operation for convenient field testing
- Optional FSX200 switchbox for one-time connection to all transformer phases
- Intuitive Windows software with automated curve comparison and reporting
These features help deliver consistent, repeatable results while reducing overall testing time.
Detect Hidden Transformer Faults
The Sweep Frequency Response Analyser is capable of identifying a wide range of transformer defects that may not be visible using conventional electrical testing.
Common applications include detecting:
- Winding displacement
- Winding deformation
- Shorted or open windings
- Core movement
- Faulty core grounds
- Broken clamping structures
- Partial winding collapse
By comparing current measurements with previous baseline tests, the Megger FRAX200 helps engineers identify developing faults before they affect transformer reliability.
FRAX200 Technical Specifications:
| Features | |
| Test Method | Sweep Frequency Response Analysis (SFRA) |
| Frequency Range | 0.1 Hz – 30 MHz |
| Dynamic Range | >150 dB |
| Maximum Measurement Points | Up to 32,000 |
| Communications | USB-C and Bluetooth |
| Battery | Rechargeable lithium-ion |
| Weight | Approx. 2.4 kg |
| Operating Temperature | -20°C to +55°C |
| Standards | IEC 60076-18, IEEE C57.149 |
Why Buy the Megger FRAX200?
Choosing the Megger FRAX200 Sweep Frequency Response Analyser gives you a proven solution for transformer condition assessment. Its portable design, advanced diagnostics and user-friendly software make it suitable for utilities, transformer manufacturers, service providers and industrial maintenance teams.
With reliable measurements and fast testing, the Megger FRAX helps reduce transformer downtime, improve maintenance planning and extend asset life.
❓ Frequently Asked Questions (FAQ)
Q1: What is the Megger FRAX200 used for?
A. The Megger FRAX200 is used to perform Sweep Frequency Response Analysis on power transformers. It detects internal mechanical or electrical changes by comparing current measurements with previous transformer fingerprints.
Q2: What faults can the Sweep Frequency Response Analyser detect?
A. The Sweep Frequency Response Analyser can identify winding movement, winding deformation, shorted turns, core movement, broken clamping structures, faulty core grounds and other internal transformer faults.
Q3: Is the Megger FRAX 200 suitable for field testing?
A. Yes. The Megger FRAX 200 is lightweight, battery powered and includes USB-C and Bluetooth communication, making it ideal for both field and workshop applications.
Q4: Does the Megger FRAX include analysis software?
A. Yes. The Megger FRAX includes Windows software with automated curve comparison, reporting and data management, with no recurring software licence fees.
Request a Quote
Looking for expert advice on transformer diagnostic testing? Contact our team today to discuss the Megger FRAX200 Sweep Frequency Response Analyser, request a competitive quotation or find the right test solution for your application.